Power – Rockwell Automation 1403-DM_LM_MM Powermonitor II Instruction Sheet User Manual

Page 48

Advertising
background image

4-12

General Operation

1403-IN001A-US-P

Power

Table 4.5 displays the Power Metering information
provided by the Powermonitor II. The gray scale
indicates which parameters are available through the
Display Module, the Smart Communication Card, or
both.

The power quantities (kW, kWH, kVAR, kVARH,
and power factor) measured by the Powermonitor II
are four-quadrant measurements. This allows the user
to individually determine the magnitude and
direction of both the real power flow and the reactive
power flow. Figure 4.3 indicates the relationship
between these quantities and the numeric signs used
by the Powermonitor II to convey the information.

Figure 4.3 Power Metering

Display Module and Smart Communication Card

Display Module Only

Smart Communication Card Only

I

IV

II

III

Pf = 1

+kVAR (Import)

kVARHR-F (Forward)

90°

Pf = 0

-kVAR (Export)

kVARHR-R(Reverse)

270°

Pf = 100%

+kW (Import)

kWH-F

(Forward)

Pf = 100%

-kW(Export)

kWH-R

(Reverse)

180°

(Power Factor

Lagging)

(-)

(Power Factor

Lagging)

(-)

(Power Factor

Leading)

(+)

(Power Factor

Leading)

(+)

Table 4.5 Power Metering

Parameter

Description

Range

Units

Phase 1 Power

Power of phase 1 signed to show direction.

0 to 999.9x10

22

Watts

Phase 2 Power

Power of phase 2 signed to show direction.

0 to 999.9x10

22

Watts

Phase 3 Power

Power of phase 3 signed to show direction.

0 to 999.9x10

22

Watts

3-Phase Total Power

Total power of phase 1, 2, and 3 signed to show direction.

0 to 999.9x10

22

Watts

Phase 1 Reactive Power

Reactive power of phase 1 signed to show direction.

0 to 999.9x10

22

Vars

Phase 2 Reactive Power

Reactive power of phase 2 signed to show direction.

0 to 999.9x10

22

Vars

Phase 3 Reactive Power

Reactive power of phase 3 signed to show direction.

0 to 999.9x10

22

Vars

3-Phase Total Reactive Power

Total reactive power of phase 1, 2, and 3 signed to show
direction.

0 to 999.9x10

22

Vars

Phase 1 Apparent Power

Apparent power of phase 1.

0 to 999.9x10

22

VA

Phase 2 Apparent Power

Apparent power of phase 2.

0 to 999.9x10

22

VA

Phase 3 Apparent Power

Apparent power of phase 3.

0 to 999.9x10

22

VA

3-Phase Total Apparent Power

Total apparent power of phase 1, 2, and 3.

0 to 999.9x10

22

VA

Phase 1 True Power Factor

The ratio between the power and apparent power for phase
1; this value is signed to show lead (+) or lag (-).

-100 to 100

Percent

Phase 2 True Power Factor

The ratio between the power and apparent power for phase
2; this value is signed to show lead (+) or lag (-).

-100 to 100

Percent

Phase 3 True Power Factor

The ratio between the power and apparent power for phase
3; this value is signed to show lead (+) or lag (-).

-100 to 100

Percent

Total True Power Factor

The ratio between the power and apparent power for phase
1, 2, and 3; this value is signed to show lead (+) or lag (-).

-100 to 100

Percent

Phase 1 Distortion Power Factor

The ratio between the magnitude of the fundamental and the
sum of the magnitudes for all of the current harmonics for
phase 1.

(1)

0 to 100

Percent