Rockwell Automation 1403-DM_LM_MM Powermonitor II Instruction Sheet User Manual

Page 67

Advertising
background image

General Operation

4-31

1403-IN001A-US-P

Display Module # 1, #2, #3 Firmware Revision
Number

This parameter returns the firmware revision number
of the respective Display Module connected to the
fiber loop. It is available only through the Smart
Communication Card. This value is returned as an
integer such that 1.00 is represented as 100.

Master Module Auxiliary Frequency

This parameter returns the frequency of the AC
signal applied to the Auxiliary Voltage input to the
Powermonitor II when the configuration parameter
“Vaux Voltage Mode” is set to AC (or 0). This value
can only be viewed through the Smart
Communication Card.

Master Module Fiber Loop Back Status

To perform a fiber loop back test follow these steps:

1. Remove any fiber optic cable connecting the

Display Modules.

2. Install a single fiber optic cable from the transmit

(Tx) port to the receive (Rx) port on the Master
Module.

3. Initiate a read of the Diagnostic/Status table via

the Smart Communication Card.

4. Examine the Master Module Fiber Loop Back

Status word within the Diagnostic/Status table.

Master Module EEPROM Status

Master Module Device ID

This parameter returns the factory pre-programmed
value which is used as the default serial address if the
optional Cat. No. 1403-NSC Smart Communication
Card is installed. The value is within the range 0-250
inclusive.

General Purpose Status Bits

BT Error Status Word 1

This word returns the Size/ID of the last block
written to the Powermonitor II through the Smart
Communication Card if any invalid data was
included in that block.

BT Error Status Word 2

This word returns the parameter number of the
invalid data item included in the last block written.
The last block written is identified by BT Error
Status Word 1.

Value
Returned

Description

0

A single fiber optic cable is incorrectly connected.

There may be a problem with the Master Module
fiber optic transceivers.

1

The fiber optic loop back test has passed.

Bits

Hex

Description

bit 0

0001h

Summary status

bit 1

0002h

Invalid configuration data status

bit 2

0004h

Calibration block checksum status

bit 3

0008h

Factory configuration block checksum
status

bit 4

0010h

Configuration block 1 checksum status

bit 5

0020h

Configuration block 2 checksum status

bit 6

0040h

Read write status

bit 7

0080h

Transfer status

bit 8

0100h

Block write in progress status

bits 9-15

Reserved for factory use

Bits

Hex

Description

bit 0

(1)

(1) Available on 1403-MM only.

0001h

Oscillogram triggered and complete

bit 1

0002h

Snapshot buffer full

bit 2

1

0004h

Oscillogram triggered by a setpoint action

bits 3-15

Reserved for factory use