Demand

Table 4.2 displays the Demand Configuration items
for Powermonitor II. The gray scale indicates which
parameters are configured by the Display Module,
the Smart Communication Card, or both.

Display Module and Smart Communication Card

Display Module Only

Smart Communication Card Only

Table 4.2 Demand Configuration

Parameter

Description

Range

Default

User

Setting

Demand Period Length

Specifies the desired period for demand measurement.
1 to 99 The internal clock is used to measure the period
(in minutes) for both the actual and projected demand
values.
0 An external pulse connected to Status Input #4 is
required to define the period for the actual demand
values while disabling the projected demand values.
-1 to -99 An external pulse connected to Status Input #4
is required to define the period for the actual demand
values while using the internal clock for the projected
demand values.

-99 to 99

1

Number of Demand
Periods

Specifies the number of demand periods to average for
demand measurement.

1 to 15

1

Pulse Output

Determines which relay to be used as a pulsed output
based on a user specified metering parameter.

0 = None
1 = Relay 1
2 = Relay 2

0 = None

Pulse Parameter

Specifies which parameter is used for the pulse output
relay.

0 = kWh Forward
1 = kWh Reverse
2 = kVarh Forward
3 = kVarh Reverse

0 = kWh
Forward

Pulse Increment

Defines how many increments of the specified metering
parameter must occur before the relay is pulsed.

1 to 32766

1

Pulse Width

Defines the duration of the pulse in milliseconds.

40 to 2000

100

Defines “kyz style” transitional pulse

0