Rockwell Automation 1403-DM_LM_MM Powermonitor II Instruction Sheet User Manual
Page 45

General Operation
4-9
1403-IN001A-US-P
Demand
Table 4.2 displays the Demand Configuration items
for Powermonitor II. The gray scale indicates which
parameters are configured by the Display Module,
the Smart Communication Card, or both.
Display Module and Smart Communication Card
Display Module Only
Smart Communication Card Only
Table 4.2 Demand Configuration
Parameter
Description
Range
Default
User
Setting
Demand Period Length
Specifies the desired period for demand measurement.
1 to 99 The internal clock is used to measure the period
(in minutes) for both the actual and projected demand
values.
0 An external pulse connected to Status Input #4 is
required to define the period for the actual demand
values while disabling the projected demand values.
-1 to -99 An external pulse connected to Status Input #4
is required to define the period for the actual demand
values while using the internal clock for the projected
demand values.
-99 to 99
1
Number of Demand
Periods
Specifies the number of demand periods to average for
demand measurement.
1 to 15
1
Pulse Output
Determines which relay to be used as a pulsed output
based on a user specified metering parameter.
0 = None
1 = Relay 1
2 = Relay 2
0 = None
Pulse Parameter
Specifies which parameter is used for the pulse output
relay.
0 = kWh Forward
1 = kWh Reverse
2 = kVarh Forward
3 = kVarh Reverse
0 = kWh
Forward
Pulse Increment
Defines how many increments of the specified metering
parameter must occur before the relay is pulsed.
1 to 32766
1
Pulse Width
Defines the duration of the pulse in milliseconds.
40 to 2000
100
Defines “kyz style” transitional pulse
0