Cumulative power – Rockwell Automation 1403-DM_LM_MM Powermonitor II Instruction Sheet User Manual

Page 50

Advertising
background image

4-14

General Operation

1403-IN001A-US-P

Cumulative Power

Table 4.6 displays the Cumulative Power Metering
information provided by the Powermonitor II. The
gray scale indicates which parameters are available
through the Display Module, the Smart
Communication Card, or both.

Display Module and Smart Communication Card

Display Module Only

Smart Communication Card Only

Table 4.6 Cumulative Power

Parameter

Description

Range

Units

Kilo-Watt Hours Forward

The total forward (+) power consumed.

0 to 1.0x10

12

kWh

Kilo-Watt Hours Reverse

The total reverse (-) power consumed.

0 to 1.0x10

12

kWh

Kilo-Watt Hours Net

The total forward and reverse power consumed.

0 to 1.0x10

12

kWh

Kilo-Var Hours Forward

The total forward (+) reactive power consumed.

0 to 1.0x10

12

kVarh

Kilo-Var Hours Reverse

The total reverse (-) reactive power consumed.

0 to 1.0x10

12

kVarh

Kilo-Var Hours Net

The total forward and reverse reactive power consumed.

0 to 1.0x10

12

kVarh

Current Demand

The calculated demand for average current.

0 to 999.9x10

22

Amps

Watt Demand

The calculated demand for total power.

0 to 999.9x10

22

Watts

Var Demand

The calculated demand for total reactive power.

0 to 999.9x10

22

Vars

VA Demand

The calculated demand for total apparent power.

0 to 999.9x10

22

VA

Projected Current Demand #1 The instantaneous demand for average current.

0 to 999.9x10

22

Amps

Projected Watt Demand #1

The instantaneous demand for total power.

0 to 999.9x10

22

Watts

Projected Var Demand #1

The instantaneous demand for total reactive power.

0 to 999.9x10

22

Vars

Projected VA Demand #1

The instantaneous demand for total apparent power.

0 to 999.9x10

22

VA

Projected Current Demand #2 The first order projected demand for average current.

0 to 999.9x10

22

Amps

Projected Watt Demand #2

The first order projected demand for total power.

0 to 999.9x10

22

Watts

Projected Var Demand #2

The first order projected demand for total reactive power. 0 to 999.9x10

22

Vars

Projected VA Demand #2

The first order projected demand for total apparent power. 0 to 999.9x10

22

VA

Projected Current Demand #3 The second order projected demand for average current. 0 to 999.9x10

22

Amps

Projected Watt Demand #3

The second order projected demand for total power.

0 to 999.9x10

22

Watts

Projected Var Demand #3

The second order projected demand for total reactive
power.

0 to 999.9x10

22

Vars

Projected VA Demand #3

The second order projected demand for apparent power. 0 to 999.9x10

22

VA

Demand Elapsed Time

The elapsed time into the demand period.

0 to 999.9x10

22

Minutes

Advertising