4-24

General Operation

1403-IN001A-US-P

Whenever a setpoint event occurs, the setpoint setup
information is also logged. This information is
viewed via the Display Module by pressing the Enter
key (

) when the setpoint event is displayed. This

information can also be retrieved via the Smart
Communication Card.

Snapshot Log

The snapshot log consists of 50 records. Each record
consists of 46 parameters. The list of parameters is
shown in Table 4.13 and Table 4.14. This log can be
updated via a setpoint occurrence or a user-
configured schedule. A user-configured schedule can
be an interval ranging from one second to three
years. To disable scheduled updates, set the period to
zero.

The Snapshot log has two modes of operation:

Fill and Stop

Circular

Fill and Stop fills the buffer and stops when it is full.
The buffer resumes recording information when the
Snapshot log is cleared.

Circular continuously fills the buffer. When the
buffer is full, old data is overwritten.

The Snapshot log information is retrieved through
the Smart Communication Card. All data is logged
together. However, for communication purposes
only, the log is divided into two blocks.

Table 4.12 Self-test Error Codes

Bits

Hex

Description

bit 0

0001h

Master Module ROM Status

bit 1

0002h

Master Module RAM Status

bit 2

0004h

Master Module EEPROM Status

bit 3

0008h

Master Module Non-volatile RAM Status

bit 4

0010h

Master Module Power Supply Status

bit 5

0020h

Master Module Data acquisition Status

bit 6

0040h

Master Module Real Time Clock Status

bit 7

0080h

Smart Communication Card Status

bit 8

0100h

Display Module Status

bit 9

0200h

Master Module Watchdog Timer Status

bits 10-
15

Reserved for factory use