2-16

Installation

1403-IN001A-US-P

Analog Input

This input is intended to accept input signals of zero
to one volt AC, 50/60 Hz, rms or plus/minus (±) 1.4
VDC.

Use twisted pair or shielded pair cable to reduce the
level of noise that may be induced on this low level
signal.

Do not use ground as a return path. A Ground
Potential Rise will add to or subtract from the input
signal level and affect the reading.

Relay Outputs

(Isolation Ratings = 2500V)

Figure 2.14 shows one of the internal Form C Relay
contacts along with an example of customer wiring to
a supply voltage and two loads.

Figure 2.14 Control Relay Connections

Status Inputs

All Status Inputs are common to an internal 24VDC
source on the SCOM terminal. Status input terminals
1-4 are positive polarity and SCOM is negative
polarity.

To prevent ground loops, each wire run to a Status
Input should have an accompanying return wire
connected to the SCOM (the common point for all
Status Inputs). (If more than two Status Inputs are
used, an external terminal block is recommended.)

Table 2.1 Contact Ratings

Rating

50/60 Hz AC rms

DC

Maximum Resistive
Load Switching

10A at 250V
(2500VA)

10A at 30V and
0.25A at 250V

Minimum Load
Switching

10mA at 24V

10mA at 24V

UL 508, CSA 22.2,
IEC Rating Class

B300

Q300

Maximum Make
Values Inductive Load

30A at 120V
15A at 240V
(3600VA)

0.55A at 125V
0.27A at 250V
(69VA)

Maximum Break
Values Inductive Load

3A at 120V
1.5A at 240V
(360VA)

0.55A at 125V
0.27A at 250V
(69VA)

Maximum Motor Load
Switching

1/3 HP at 125V
1/2 HP at 250V

Table 2.2 Relay Life

Parameter

Number of Operations

Mechanical

5 X 10

6

Electrical

1 X 10

5

!

ATTENTION: Do not apply an
external voltage to a Status Input.
These inputs have an internal source
and are intended for dry contact input
only. Applying a voltage may damage
the associated input or internal power
supply.

V1

V2

V3

N

Fiber

Rx

Fiber

Tx

I1+

I2+

I3+

I4+

S1

S2

S3

S4

Scom

L/+

R14

R11

R12

R24

R21

R22

Acom

Ain

N

Voltage
Inputs

Status
Inputs

Display
Module Fiber

Current
Inputs

Power

GRD

N/-

I1-

I2-

I3-

I4-

PM-II
Master
Module

L1

L2

Load

Load

10A Fuse

Analog
Input

Relay
Outputs