4-28

General Operation

1403-IN001A-US-P

Oscillography (1403-MM only)

The Powermonitor II provides two types of
oscillography. Both are triggered simultaneously and
sampled at 10.8 kilo-hertz. The types are:

Simultaneous 7-channel 2-cycle oscillogram

User configurable simultaneous 2-channel 12-
cycle oscillogram with up to eight cycles of
pretrigger data

These oscillograms can be triggered manually or as
the result of a setpoint. Oscillogram configuration
and retrieval can only be accomplished through the
Smart Communication Card.

Oscillography has two modes of operation:

Hold

Overwrite

Hold fills a buffer when an oscillograph is triggered,
and it does not allow another oscillograph to trigger
until the Master Module is commanded to cancel the
hold. Overwrite allows oscillographs to be
overwritten when multiple triggers occur.

The pretrigger data of the 2-channel simultaneous
12-cycle oscillogram is disabled by setting the
number of pretrigger cycles to a -1. This action
makes the real time metering update slightly faster.

Self-test/Diagnostic Information

The Powermonitor II and its accessories have an
extensive array of internal self-tests. Complete self-
tests are executed at device powerup, and critical
tests are continuously run during operation of the
device. The results of these self-tests are used to
insure the integrity of the information provided by
Powermonitor II and its accessories. Improper self-
test results cause the device to cease normal
operation.

Bulletin Number

For the Powermonitor II, this parameter returns 1403.

Master Module Firmware Revision Number

This parameter returns the firmware revision number
of the Master Module. This value is returned through
the Smart Communication Card as an integer such
that 1.00 is represented as 100.

Options Bit Field

69

(1)

Phase 2 Current K-factor

70

Phase 3 Voltage IEEE THD

71

Phase 3 Voltage IEC THD

72

(1)

Phase 3 Voltage TIF

73

(1)

Phase 3 Voltage Crest Factor

74

(1)

Phase 3 Voltage K-factor

75

Phase 3 Current IEEE THD

76

Phase 3 Current IEC THD

77

(1)

Phase 3 Current TIF

78

(1)

Phase 3 Current Crest Factor

79

(1)

Phase 3 Current K-factor

80

Phase 4 Current IEEE THD

81

Phase 4 Current IEC THD

82

(1)

Phase 4 Current TIF

83

(1)

Phase 4 Current Crest Factor

84

(1)

Phase 4 Current K-factor

(1) Available on 1403-MM only.

Table 4.15 The Parameter Listing for the Min/Max Log

Parameter Number

Parameter Description

Table 4.16 Options Bit Field

Bits

Hex

Description

bit 0

0001h High voltage power supply (Type A)

bit 1

0002h Low voltage power supply (Type B)

bit 2

0004h 1 Amp Master Module current input (Type 01)

bit 3

0008h 5 Amp Master Module current input (Type 05)

bit 4

0010h Limited metering

bit 5

0020h Reserved for future use

bits 6-15

Reserved for factory use