Rockwell Automation 1403-DM_LM_MM Powermonitor II Instruction Sheet User Manual

Page 44

Advertising
background image

4-8

General Operation

1403-IN001A-US-P

Channel A
12-Cycle Oscillograph

¨

Used to select which of the seven input channels is
captured for channel A when an oscillograph is triggered.

1 = Phase 1
Voltage
2 = Phase 1
Current
3 = Phase 2
Voltage
4 = Phase 2
Current
5 = Phase 3
Voltage
6 = Phase 3
Current
7 = Phase 4
Current

1 = Phase 1
Voltage

Channel B
12-Cycle Oscillograph

¨

Used to select which of the seven input channels is
captured for channel B when an oscillograph is triggered.

1 = Phase 1
Voltage
2 = Phase 1
Current
3 = Phase 2
Voltage
4 = Phase 2
Current
5 = Phase 3
Voltage
6 = Phase 3
Current
7 = Phase 4
Current

2 = Phase 1
Current

Oscillography Type

¨

Determines whether the existing oscillograph is
overwritten or remains buffered until commanded when a
new oscillograph is triggered.

0 = Hold
1 = Overwrite

1 =
Overwrite

Number of Oscillograph
Pretrigger Cycles

¨

Indicates the number of cycles buffered prior to the trigger
of a 12-cycle oscillograph. This function can be disabled
by setting this value to -1 to improve the speed of the real
time metering update rates.

-1 to 8

1

(1) Available on 1403-MM only.

Table 4.1 General Configuration

Parameter

Description

Range

Default

User

Setting