Rockwell Automation 1403-DM_LM_MM Powermonitor II Instruction Sheet User Manual
Page 44

4-8
General Operation
1403-IN001A-US-P
Channel A
12-Cycle Oscillograph
¨
Used to select which of the seven input channels is
captured for channel A when an oscillograph is triggered.
1 = Phase 1
Voltage
2 = Phase 1
Current
3 = Phase 2
Voltage
4 = Phase 2
Current
5 = Phase 3
Voltage
6 = Phase 3
Current
7 = Phase 4
Current
1 = Phase 1
Voltage
Channel B
12-Cycle Oscillograph
¨
Used to select which of the seven input channels is
captured for channel B when an oscillograph is triggered.
1 = Phase 1
Voltage
2 = Phase 1
Current
3 = Phase 2
Voltage
4 = Phase 2
Current
5 = Phase 3
Voltage
6 = Phase 3
Current
7 = Phase 4
Current
2 = Phase 1
Current
Oscillography Type
¨
Determines whether the existing oscillograph is
overwritten or remains buffered until commanded when a
new oscillograph is triggered.
0 = Hold
1 = Overwrite
1 =
Overwrite
Number of Oscillograph
Pretrigger Cycles
¨
Indicates the number of cycles buffered prior to the trigger
of a 12-cycle oscillograph. This function can be disabled
by setting this value to -1 to improve the speed of the real
time metering update rates.
-1 to 8
1
(1) Available on 1403-MM only.
Table 4.1 General Configuration
Parameter
Description
Range
Default
User
Setting