Rockwell Automation 1403-DM_LM_MM Powermonitor II Instruction Sheet User Manual

Page 65

Advertising
background image

General Operation

4-29

1403-IN001A-US-P

Overall Status

The overall status word is a summary of the
individual self-test summary status bits. This allows
the user to check a single word to determine the
device status.

Note:

The overall status word is logged in the event
log when a self-test is not successful and the
OK LED of the product is not illuminated.
The logged event is shown on the Display
Module using the code ST####, where ####
is a four digit hexadecimal number made up
of a combination of all of the bits set to 1 in
the overall status word.

Master Module ROM Status

Master Module RAM Status

Master Module NVRAM Status

Master Module Power Supply Status

Master Module Data Acquisition Status

Master Module Watchdog Timer Status

Bits

Hex

Description

bit 0

0001h

Master Module ROM status

bit 1

0002h

Master Module RAM status

bit 2

0004h

Master Module EEPROM status

bit 3

0008h

Master Module non-volatile RAM
status

bit 4

0010h

Master Module power supply status

bit 5

0020h

Master Module data acquisition status

bit 6

0040h

Master Module real time clock status

bit 7

0080h

Smart Communication Card status

bit 8

0100h

Display Module status

bit 9

0200h

Master Module watchdog timer status

bits 10-
15

Reserved for factory use

Bits

Hex

Description

bit 0

0001h

Summary status

bit 1

0002h

Checkless status

bits 2-15

Reserved for factory use

Bits

Hex

Description

bit 0

0001h

Summary status

bit 1

0002h

Read/write status

bits 2-15

Reserved for factory use

Bits

Hex

Description

bit 0

0001h

Summary status

bit 1

0002h

Event log checksum status

bit 2

0004h

Snapshot log checksum status

bit 3

0008h

kW checksum status

bit 4

0010h

Master Module log checksum status

bit 5

0020h

Power down timestamp checksum
status

bit 6

0040h

Status input counter checksum
status

bits 7-15

Reserved for factory use

Bits

Hex

Description

bit 0

0001h

Summary status

bit 1

0002h

Plus 12V supply too high

bit 2

0004h

Plus 12V supply too low

bit 3

0008h

Minus 12V supply too low

bit 4

0010h

Minus 12V supply too high

bits 5-15

Reserved for factory use

Bits

Hex

Description

bit 0

0001h

Summary status

bit 1

0002h

Sample clock generation status

bit 2

0004h

Data bus connection status

bit 3

0008h

Address test status

bit 4

0010h

Internal calibration status

bit 5

0020h

FIFO full interrupt status

bit 6

0040h

Internal reference status

bit 7

0080h

Low voltage status

bits 8-15

Reserved for factory use

Bits

Hex

Description

bit 0

0001h

Summary status

bit 1

0002h

Response time status

bit 2

0004h

Watchdog fired status

bits 3-15

Reserved for factory use

Advertising