Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Chapter 6

Configure the Module for a SmartGuard Controller

Auto-addressing with a
1734-PDN Adapter

With sequential auto-addressing, the leftmost node address is configured and a
parameter is set in that module to automatically assign addresses to the nodes
residing to the right of the module. The leftmost node can be a
POINT Guard I/O module or a standard POINT I/O module.

Follow these steps to use the auto-address feature.

1. Reset any modules that you are not sure are out-of-box.

2. Attach the first module to the 1734-PDN adapter.

3. Use the node commissioning tool to set the node address of this module.

4. Attach the additional nodes to the right of the module used in

steps

2

and

3

.

5. Perform the auto-address feature on the module used in steps

2

and

3

.

A. Set the address of the leftmost I/O module.

B. When you configure the leftmost module, set Sequential AutoAddress to
‘Sequential Address’.

The module sequences the rest of the
modules to its right in the group.