For mo – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 178

Advertising
background image

178

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Appendix C

Specifications

Figure 59 - System Temperature Derating When a 1734-IE4S Module Is Used

Emissions

CISPR 11 (IEC 61000-6-4): Class A

ESD immunity

IEC 61000-4-2:
4 kV contact discharges (1734-IB8S, Series B and 1734-OB8S, Series B
only)
6 kV contact discharges (1734-IB8S, Series A; 1734-OB8S, Series A; and
1734-IE4S)
8 kV air discharges (all modules)

Radiated RF immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:
±3 kV @ 5 kHz on power ports (1734-IE4S only)
±3 kV @ 5 kHz shielded on signal ports (1734-IE4S only)
±3 kV @ 5 kHz on signal ports (1734-IB8S, 1734-OB8S only)

Surge transient immunity

IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
(1734-IB8S and 1734-OB8S only)
± 1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
(1734-IE4S only)
±2 kV line-earth (CM) on shielded ports (1734-IE4S only)

Conducted RF immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

(1) See

Figure 59

,

System Temperature Derating When a 1734-IE4S Module Is Used

.

Attribute

Value

1.2 W/cm

(3 W /in.)

0.8W/cm

(2 W /in.)

-20°C

(-4 °F)

40°C

(104 °F)

55°C

(131°F)

See

Placing Series A Digital and Analog Modules on page 48

for examples.

Advertising