Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Chapter 5

Configure the Module in a GuardLogix Controller System

e. From the Input Data pull-down menu, choose Safety or None.

f. From the Output Data pull-down menu, choose from the following

options.

Choose

Description

Safety

These tags are created for the target module:
RunMode for module mode
ConnectionFaulted for communication status
Safety Data for safety inputs from the module

Choose

Description

None

Results in an input only connection to the module. Inputs and status are read, but no
outputs are written. You can still use the test outputs as pulse test outputs or a power
supply. If you are not controlling the module’s test outputs via application logic, this is
the recommended setting.

Test

(1)

(1) To have this choice from the pull-down menu, you must choose ‘This Controller’ from the Configured By pull-down

menu.

Creates these tags to enable application logic control of the test outputs on the module.
This selection allows the test outputs to be used as standard outputs and muting
outputs.

IMPORTANT

When test outputs are configured as standard outputs, they
must not be used for safety purposes.