Environmental specifications – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 177

Advertising
background image

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

177

Specifications

Appendix C

Environmental Specifications

Power bus, operating voltage range

19.2…28.8V DC, Class 2

Power bus current (no load), max

50 mA

Input filter time, OFF to ON

(4)

0…126 ms (in 6 ms increments)

Input filter time, ON to OFF

(4)

Terminal base screw torque

See terminal base specifications

Indicators

1 yellow lock status indicator
1 green/yellow power status indicator
8 I/O channel status indicators

Keyswitch positions (left and right)

Key 1 = 8 (left); Key 2 = 2 (right)

Pilot duty rating

Not rated

North America temp code

T4

IEC temp code

T4

Enclosure type rating

None (open-style)

Wiring category

(5)

2 - on signal ports

Wire size

Determined by installed terminal block

Weight, approx.

62.4 g (2.2 oz)

Dimensions (HxWxD), approx. (without terminal block)

77 x 25 x 55 mm (3.03 x 0.98 x 2.17 in.)

(1) To comply with UL certification requirements, field power must be supplied from a single Class 2‐compliant power supply

(See

Choosing a Power Supply on page 45

) which limits available field power to 100VA. Therefore, the aggregate current of outputs

per module is limited to a maximum set by the 100VA limit (unless derated further as shown) for applications that require UL
listing.

(2) Maximum power dissipation applies when using 28.8V DC module supply and maximum power dissipated with all eight outputs in

the ON state.

(3) Typical power dissipation applies when using 24V DC module supply and nominal power dissipated with all eight outputs in the ON

state.

(4) Input off-to-on filter time is the time from a valid input signal to recognition by the module. Input on-to-off time is the time from a

valid input signal to recognition by the module.

(5) Use this conductor category information for planning conductor routing. Refer to the Industrial Automation Wiring and Grounding

Guidelines, publication

1770-4.1

.

Attribute

1734-OB8S Series B

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…55 °C (-4…131 °F)

(1)

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)

Temperature, surrounding air, max

55 °C (131 °F)

(1)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing

Vibration

IEC 60068-2-6, (Test Fc, Operating)
5 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock) 50 g

Corrosives

1734-IB8S and 1734-OB8S Series B only: G2 (ISA S71.04)