Replacing POINT Guard I/O Modules

Chapter 8

3. Click the Safety tab.

4. Click Reset Ownership.

5. Click OK.

6. Follow your company-prescribed procedures to functionally test the

replaced I/O module and system and to authorize the system for use.

Replacement with ‘Configure Always’ Enabled

When the ‘Configure Always’ feature is enabled, the controller automatically
checks for and connects to a replacement module that meets all of the following
requirements:

The controller has configuration data for a compatible module at that

network address.

The module is in out-of-box condition or has an SNN that matches the

configuration.

If the project is configured for ‘Configure Always’, follow the appropriate steps to
replace a POINT Guard I/O module.

ATTENTION: Enable the Configure Always’ feature only if the entire CIP Safety
Control System is not being relied on to maintain SIL 3 behavior during the
replacement and functional testing of a module.

Do not place modules that are in the out-of-box condition on a CIP Safety network
when the Configure Always feature is enabled, except while following this
replacement procedure.