Output assemblies, Analog input assemblies, Output assemblies analog input assemblies – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 192

Advertising
background image

192

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Appendix F

I/O Assemblies

Output Assemblies

Analog Input Assemblies

Table 22 - 1734-OB8S Input Assemblies

Instance
Decimal (hex)

Connection
Type

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

580 (244h)

Safety and
Standard

0

Safety Output 7 Safety Output 6 Safety Output

5

Safety Output
4

Safety Output
3

Safety Output
2

Safety Output
1

Safety Output
0

1028 (404h)

Safety and
Standard

0

Safety Output 7 Safety Output 6 Safety Output

5

Safety Output
4

Safety Output
3

Safety Output
2

Safety Output
1

Safety Output
0

1

Safety Output

Monitor 7

Safety Output
Monitor 6

Safety Output
Monitor 5

Safety Output
Monitor 4

Safety Output
Monitor 3

Safety Output
Monitor 2

Safety Output
Monitor 1

Safety Output
Monitor 0

1044 (414h)

Safety and
Standard

0

Safety Output

Monitor 7

Safety Output
Monitor 6

Safety Output
Monitor 5

Safety Output
Monitor 4

Safety Output
Monitor 3

Safety Output
Monitor 2

Safety Output
Monitor 1

Safety Output
Monitor 0

1

Reserved

Combined
Output

Reserved

Output Power
Error

Reserved

Table 23 - Output Assemblies for all POINT Guard I/O Modules

Instance Decimal
(hex)

Module

Connection
Type

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

33 (21h)

1734-IB8S

Safety

(1)

0

Reserved

Standard
Output 3

Standard
Output 2

Standard
Output 1

Standard
Output 0

564 (234h)

1734-OB8S

Safety Only

0

Safety
Output 7

Safety
Output 6

Safety
Output 5

Safety
Output 4

Safety
Output 3

Safety
Output 2

Safety
Output 1

Safety
Output 0

770 (302h)

1734-IE4S

Safety

0

Reserved

Reserved

Reserved

Reserved

Reset Tach

3

(2)

Reset Tach

2

(2)

Reset Tach

1

(2)

Reset Tach

0

(2)

(1) Only outputs 1 and 3 are configurable to Muting or Test Outputs. This assembly is accessible only over a Safety connection.
(2) When set (1), this bit specifies a reset of an overfrequency condition on the tachometer counter. Clear this bit to allow the tachometer channel to operate.

Table 24 - 1734-IE4S Input Assemblies

Instance
Decimal (hex)

Connection
Type

Byte

High Byte

Low Byte

402 (192h)

Safety and
Standard

0, 1

Input 0

Input 0

2, 3

Input 1

Input 1

4, 5

Input 2

Input 2

6, 7

Input 3

Input 3

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

8

Reserved

Reserved

Reserved

Reserved

Ch 3 Input

Status

Ch 2 Input

Status

Ch 1 Input

Status

Ch 0 Input

Status

Advertising