Technical specifications for series b modules, Safety digital input module specifications, Technical – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 173: Specifications for series b modules, For s

Advertising
background image

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

173

Specifications

Appendix C

Technical Specifications for
Series B Modules

Safety Digital Input Module Specifications

Attribute

1734-IB8S Series B

Safety Input

Inputs per module

8

Input type

Current sinking

Voltage, on-state input

11…30V DC, 3.5 mA @ 40 °C (104 °F), Class 2
11…28.8V DC, 3.5 mA @ 55 °C (131 °F), Class 2

1734‐IB8S Series B temperature versus safety input
voltage (max) ‐ derating for both horizontal and vertical
installations

Voltage, off-state input, max

5V DC

Current, on-state input, min

3.3 mA

Current, off-state, max

1.3 mA

IEC 61131-2 (input type)

Type 3

Reaction time

<16.2 ms

Pulse Test Output

Output type

Current sourcing

Number of sources (T0, T1M, T2, T3M)

4

Test output current (each output point)

0.7 A @ 40 °C (104 °F)
0.5 A @ 55 °C (131 °F)

1734‐IB8S Series B temperature versus current per test
output point ‐ derating for both horizontal and vertical
installations

Aggregate current of test outputs per module

2.8 A @ 40 °C (104 °F)
0.55 A @ 55 °C (131 °F)

30V

-20 °C
(-4 °F)

40 °C
(104 °F)

55 °C
(131 °F)

28.8V

0.7 A

-20 °C
(-4 °F)

40 °C
(104 °F)

55 °C
(131 °F)

0.5 A

Advertising