Safety digital output module specifications – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 176

Advertising
background image

176

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Appendix C

Specifications

Safety Digital Output Module Specifications

Attribute

1734-OB8S Series B

Safety Output

Outputs per module

8

Output type

Current sourcing

Output current (each output point), max

1 A @ 40 °C (104 °F)
0.5 A @ 55 °C (131 °F)

1734‐OB8S Series B temperature versus current per
output point ‐ derating for both horizontal and vertical
installations

Aggregate current of outputs per module

(1)

8 A (4 A per terminal base) @ 40 °C (104 °F)
2A (1A per terminal base) @ 55 °C (131 °F)

1734‐OB8S Series B temperature versus aggregate current
per module ‐ derating for both horizontal and vertical
installations

(1)

Pulse width

475

μs

Pulse period

575 ms

Maximum field capacitance limit permitted per output

950 nF

On-state voltage drop

0.165V

Leakage current, max

0.1 mA

Short-circuit detection

Yes (short high and low and cross-circuit detect)

Short-circuit protection

Electronic

Reaction time

<6.2 ms

POINTBus

POINTBus current, max

125 mA

Power dissipation, max

(2)

3.5 W

Thermal dissipation, max

11.96 BTU/hr

Power dissipation, typical

(3)

2.5 W

Isolation voltage

50V (continuous), Basic Insulation Type between field
side and system
No isolation between individual channels
Type tested at 860V AC DC for 60 s

Power bus, operating supply voltage

24V DC nom, Class 2

1 A

0.5 A

-20 °C
(-4 °F)

40 °C
(104 °F)

55 °C
(131 °F)

8 A

2 A

-20 °C
(-4 °F)

40 °C
(104 °F)

55 °C
(131 °F)