Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual
Page 146
Advertising

146
Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
Chapter 8
Replacing POINT Guard I/O Modules
1. Remove the old I/O module and install the new module.
2. Right-click your POINT Guard I/O module and choose Properties.
3. Click the Safety tab.
4. Click Reset Ownership.
5. Click OK.
6. Follow your company-prescribed procedures to functionally test the
replaced I/O module and system and to authorize the system for use.
If
then
the module is in out-of-box condition
go to step
.
No action is needed for the GuardLogix controller to take
ownership of the module.
an SNN mismatch error occurs
go to the next step to reset the module to out-of-box condition.