Add and configure the ethernet bridge module – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 74

Advertising
background image

74

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Chapter 5

Configure the Module in a GuardLogix Controller System

Add and Configure the
Ethernet Bridge Module

Follow this procedure to add and configure the Ethernet bridge module. In this
example, we use a 1756 GuardLogix controller.

1. From the I/O Configuration tree, right-click 1756 Backplane, 1756-Axx

and choose New Module.

2. In the Select Modules dialog box, check Communication and

Allen-Bradley.

3. Choose an Ethernet module from the list and click Create.

In this example, we chose the 1756-EN2T bridge module. CIP Safety is
supported by these module revisions.

4. Specify the properties for the new module.

a. In the Name field of the New Module dialog box, type the name of the

Ethernet bridge module.

b. In the Description field, type an optional description.
c. In the IP Address field, type the IP address.
d. In the Slot field, choose the slot number.

Cat. No.

Compatible Major Revision

1756-EN2F

1 or later

1756-EN2T

1 or later

1756-ENBT

3 or later

1756-EN2TR

3 or later

1756-EN3TR

3 or later

1768-ENBT

3 or later