Table 11 – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 142

Advertising
background image

142

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Chapter 8

Replacing POINT Guard I/O Modules

controller to download the proper module configuration, and re-establish the
safety connection.

Scenario 1 - Replacement Module Is Out-of-box and Safety Signature Exists

1. Remove the old I/O module and install the new module.

2. Right-click the replacement POINT Guard I/O module and choose

Properties.

3. Click

to the right of the safety network number to open the Safety

Network Number dialog box.

4. Click Set.

Table 11 - Replacing a Module

GuardLogix Safety
Signature Exists

Replacement
Module Condition

Action Required

No

No SNN
(Out-of-box)

None. The module is ready for use.

Yes or No

Same SNN as original
safety task
configuration

None. The module is ready for use.

Yes

No SNN
(Out-of-box)

See

Scenario 1 - Replacement Module Is Out-of-box and Safety

Signature Exists on page 142

.

Yes

Different SNN from
original safety task
configuration

See

Scenario 2 - Replacement Module SNN Is Different from Original

and Safety Signature Exists on page 143.

No

See

Scenario 3 - Replacement Module SNN Is Different from Original

and No Safety Signature Exists on page 144

.