1734-ie4s safety analog input module features, Programming requirements – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 19

Advertising
background image

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

19

POINT Guard I/O Overview

Chapter 1

1734-IE4S Safety Analog Input Module Features

Connection of up to four voltage or current sensors.
Sensor power outputs are individually current-limited and monitored.
Measurement of process variables, such as temperature, pressure, or flow

rate.

Seven configurable input ranges

(±10V, ±5V, 0…5V, 0…10V, 4…20 mA, 0…20 mA, Tachometer).

Tachometer mode converts 24V DC switching signals into pulses per

second.

Single-channel or dual-channel for SIL 3-rated safety devices and

applications.

Dual-channel mode evaluates the consistency between two input signals

(channels), which allows use of the module in applications rated up to and
including SIL CL3/PLe/Cat. 4.

You can configure a discrepancy time to control how long two channels are

allowed to be discrepant before a fault is declared.

Programming Requirements

Use the minimum software versions listed here.

Cat. No.

Studio 5000 Environment
Version

(1)

(1) This version or later.

RSLogix 5000 Software
Version

(1)

(EtherNet/IP Network)

RSNetWorx for DeviceNet
Software Version

(1)

(DeviceNet Network)

1734-IB8S,
1734-OB8S

21

17

(2)

(2) If you are using digital POINT Guard I/O modules with the analog POINT Guard I/O module, you need to update the add-on

profiles to version 2.02.004 or later for the modules to be compatible with version 18 or later of RSLogix 5000 software and the
Studio 5000 environment. To find add-on profiles, go to

http://www.rockwellautomation.com/support

.

9

1734-IE4S

21

18

(3)

(3) Dual-channel Analog (DCA) safety application instruction is available in RSLogix 5000 software, version 20 or later and Studio

5000 environment, version 21 and later.