Install the Module

Chapter 4

Emergency stop button
Door monitoring switch

No

Connect the devices between T0 and I0
and I1, noting that T0 is configured for
24V power supply.

3

Connect the devices between 24V DC
and I0 and I1.

Yes

Connect the device between I0 and T0,
and I1 and T1.

4

Light Curtain

Yes

Connect the OSSD1 and OSSD2 to I0 and
I1, respectively. Connect the 24V power
supply commons.

3 or 4 based on
light curtain
being used

Connected Device

Test Pulse from
Test Output

Connection

Schematic Diagram

Safety
Category

I0

I1

T0

T1

I0

I1

T0

T1

24V DC

I0

I1

T0

T1

OSS
D2

OSS
D1

I0

I1

T0

T1

In -

24V

DC

Com

OSSD2

OSSD1