Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 162

Advertising
background image

162

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Appendix C

Specifications

1734-IB8S temperature versus current derating for both
horizontal and vertical installations

Residual voltage, max

0.3V

Output leakage current, max

0.1 mA

Short circuit protection

Yes

POINTBus

POINTBus current, max

175 mA

Power dissipation, max

(1)

3.4 W

Power dissipation, typical

2.44 W

Thermal dissipation, max

11.62 BTU/hr

Isolation voltage

50V (continuous), Basic Insulation Type between field
side and system
No isolation between individual channels
Type tested at 707V DC for 60 s

Power bus, operating supply voltage

24V DC nom

Power bus, operating voltage range

19.2…28.8V DC

Power bus current (No Load), max

25 mA

Input filter time, OFF to ON

(2)

0…126 ms (in 6 ms increments)

Input filter time, ON to OFF

(2)

Terminal base screw torque

See terminal base specifications

Indicators

1 yellow lock status indicator
1 green/yellow power status indicator
8 I/O channel status indicators

Keyswitch positions (left and right)

1734-IB8S: Key 1 = 8 (left); Key 2 = 1 (right)
1734-OB8S: Key 1 = 8 (left); Key 2 = 2 (right)

North America temp code

T4

IEC temp code

T4

Enclosure type rating

None (open-style)

Wiring category

(3)

2 - on signal ports

Wire size

Determined by installed terminal block

Weight, approx

62.4 g (2.2 oz)

Dimensions (HxWxD), approx (without terminal block)

77 x 25 x 55 mm (3.03 x 0.98 x 2.17 in.)

(1) Maximum power dissipation applies when using 28.8V DC module supply, 30V DC on all inputs and maximum power dissipated

with all four test outputs in the ON state.

(2) Input off-to-on filter time is the time from a valid input signal to recognition by the module. Input on-to-off time is the time from a

valid input signal to recognition by the module.

(3) Use this conductor category information for planning conductor routing. Refer to the Industrial Automation Wiring and Grounding

Guidelines, publication

1770-4.1

.

Attribute

1734-IB8S Series A

2.8 A

-20 °C
(-4 °F)

40 °C
(104 °F)

55 °C
(131 °F)

2.0 A

Advertising