Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual
Page 167
Advertising

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
167
Specifications
Appendix C
Step Response and Filter Response for 1734-IE4S Modules
Figure 49 - Step Response
Filter Setting
Step Response to 63%
Corner Frequency-3 dB
50 Hz
~ 25 ms
10.2 Hz
10 Hz
~ 72 ms
4.75 Hz
5 Hz
~ 125 ms
2.62 Hz
1 Hz
~ 450 ms
0.68 Hz
50 Hz
10 Hz
5 Hz
1 Hz
100%
80%
60%
63%
40%
400 ms
800 ms
1200 ms
20%
0%
0 1 2 3
4
0 ->1= ~25 ms
0 ->2= ~72 ms
0 ->3= ~125 ms
0 ->4= ~450 ms