Chapter 6

Configure the Module for a SmartGuard Controller

4. Double-click each Channel Safety Configuration group to display the

parameters for editing.

Parameter Name

Value

Description

Default

Input Mode

Not Used

External input device is not connected.

Not Used

Safety

A solid-state safety sensor is connected.

Standard

A standard device is connected.

Input Range

±10V

Input voltage range.

4…20 mA

0…5V

0…10V

±5V

4…20 mA

Input current range.

0…20 mA

Tachometer

Tachometer mode.

Latch Time

0…65,530 ms
(in 10 ms increments)

Safety input errors are latched for this time so that they can be read by the controller and are not
missed if they clear themselves too quickly. One value for all channels.

1000

Filter Setting

1 Hz

A single-pole, anti-aliasing filter of 10Hz is followed by a four-pole digital filter with these available
frequencies.

(1)

1 Hz

5 Hz

10 Hz

50 Hz

High Engineering

-30000…30000

scaling value for inputs

10000

(2)

Low Engineering

-30000…30000

scaling value for inputs

0

Sensor Power Source

External

An external power supply is used to power the analog sensors. Terminals S0…S3 on the module
are not being used.

Module

Module

Terminals S0…S3 on the module are being used to power the analog sensors.

(1) For more information on the filter frequencies and step response, see the technical specifications for the 1734-IE4S module, beginning on page

164

.

(2) 1000 for Tachometer mode.

TIP

Set this value to Module to supply power to the sensors connected to the POINT
Guard Analog Input module. This allows the module to detect a loss of sensor
power.