Configure the Module for a SmartGuard Controller

Chapter 6

5. Double-click each Engineering Units Alarms group to display parameters

for editing.

Parameter Name

Value

Description

Default

High High/Low Low Alarm
Enable

Disable

Enable or disable alarms.

Disable

Enable

High High Alarm

-32768…32767

Follow these guidelines when setting the alarm values.

The High High alarm value must be greater than or equal to the High alarm value.
The High alarm value must be greater that the Low alarm value.
The Low Low alarm value must be less than or equal to the Low alarm value.
These values are based on the Engineering units

32767

Low Low Alarm

-32768…32767

0

High Alarm

-32768…32767

32767

Low Alarm

-32768…32767

0

High High/Low Low Alarm
Deadband

0…32767

Deadband on the High High and Low Low alarms.

0

High/Low Alarm Deadband

0…32767

Deadband on the High and Low alarms.

0