Safety Digital Output Module Specifications

Attribute

1734-OB8S Series A

Safety Output

Outputs per module

8

Output type

Current sourcing

Output current (each output point)

1 A max

Pulse width

475

μs

Pulse period

575 ms

Maximum field capacitance limit permitted per output

950 nF

On-state voltage drop

0.165V

Leakage current, max

0.1 mA

Short-circuit detection

Yes (short high and low and cross-circuit fault detect)

Short-circuit protection

Electronic

Aggregate current of outputs per module

8 A (4 A per terminal base) @ 40 °C (104 °F)

1734-OB8S temperature versus current derating for both
horizontal and vertical installations

Reaction time

<6.2 ms

POINTBus

POINTBus current, max

190 mA

Power dissipation, max

(1)

4.5 W

Power dissipation, typical

3.02 W

Thermal dissipation, max

15.38 BTU/hr

Isolation voltage

50V (continuous), Basic Insulation Type between field
side and system
No isolation between individual channels
Type tested at 707V DC for 60 s

Power bus, operating supply voltage

24V DC nom

Power bus, operating voltage range

19.2…28.8V DC

Power bus current (No Load), max

75 mA

Input filter time, OFF to ON

(2)

0…126 ms (in 6 ms increments)

Input filter time, ON to OFF

(2)

Terminal base screw torque

See terminal base specifications

Indicators

1 yellow lock status indicator
1 green/yellow power status indicator
8 I/O channel status indicators

8 A

6 A

-20 °C
(-4 °F)

40 °C
(104 °F)

55 °C
(131 °F)

4 A