Half-duplex protocol chapter 11 – Rockwell Automation 1775-KA PLC-3 Communication Adapter Module User Manual User Manual

Page 146

Advertising
background image

Half-Duplex Protocol

Chapter 11

11Ć19

When a slave station’s message source and sink share a common memory
pool (as in the 1775–KA module) it may be that the message sink full
indication results from an abundance of messages in the message source,
which uses up all free pool memory. In this case, the memory can be
freed up by receiving messages from that slave station. Waiting for the
memory to clear by the action of the slave station alone may not work,
since it could be that the only way to fee up space is for the slave to send a
message to the master. This situation is illustrated in Figure 11.11.

Figure 11.11

Message Sink Full, Case 2

Full

OK

xxxx

xxxx

SINK

MASTER

LINK

SLAVE

SINK

10061–I

DLE ACK

SOURCE/

SOURCE/

BCC

DLE SOH STN

DLE STX

BCC

DLE ENQ STN

Not Full

(Timeout)

DLE STX xxxx DLE ETX

BCC

DLE SOH STN DLE STX xxxx DLE ETX

xxxx

Not Full

xxxx

xxxx DLE ETX BCC