Remote Error Codes Received from the

1773-KA Module

Appendix B

BĆ4

Local and Reply Error Code Listing for the PLC–3 Processor

Error

Error

Code

Type

Meaning

32

Local

The size of the local file involved in a file

assignment command is greater than 65,535
bytes.

34

local

A station number greater than 376 (octal)
was specified for the remote address in an
assignment command.

35

local

Attempt to send unprotected command is
invalid.

37

local

The per-packet timeout, which can be set
through LIST, ran out before a reply was
received. This means that the remote station
acknowledged (ACK) the command
message, but did not send the reply in the
allotted time. (cf. error 92)

81

reply

For diagnostic read commands:
1.A 2-byte ADDR field and a 1-byte SIZE
field are missing after the FNC byte in the
command message.
2.The number of bytes of data requested in
the SIZE field is greater than the
maximum number allowed per reply
packer (244), or SIZE is 0 (zero).
For PLC/PLC-2 read commands:
1.The required 2-byte ADDR field and
1-byte SIZE field are missing in the
command message.
2.The ADDR value is odd (that is, it does
not specify a word address).
3.The value of SIZE is 0 (zero).
4.The value of SIZE is greater than 244.
5.The SIZE value specifies an odd number
of bytes.
For PLC/PLC-2 bit write commands:
Incomplete bit description because the

Local and Reply Error Codes