Rockwell Automation 1775-KA PLC-3 Communication Adapter Module User Manual User Manual

Page 183

Advertising
background image

Message Formats

Appendix A

AĆ21

Privileged Write

Use this write command with a PLC–3 physical address as a starting
address. You use this command to download to a PLC–3 from a
computer. The destination 1775– KA module will accept this command
only after the source station has successfully transmitted a shutdown
request. The function code for this command is 8.

Command Format:

DLE

SRC

C

0

S

TNS

MD

F

TS

TNS

STX

FNC

08

DST

DLE ETX

BCC

DATA - Max of 238 bytes or 119 words

PLC-3

physical address

Reply Format:

This is the same as the reply packet format for all writes.

A. Format when the command was successfully executed

DLE

SRC

STX

DST

C

4F

S

TNS

MD

TS

TNS DLE ETX

BCC

B. Format when reporting an error

ETX

STS

DLE

SRC

STX

DST

C

4F

S

TNS

MD

TS

TNS

DLE ETX

BCC

Where the extended status byte is optional.

From a computer you use this command to ask the 1775–KA module to
initiate either a PLC–3 shutdown (if the computer has download
privileges) or a freeze on file allocations (if the computer has upload
privileges). This command halts program and I/O scanning. You cannot
issue this command until you have successfully transmitted an upload or
download request to the 1775–KA module. This command has a function
code of 7.

Advertising