Rockwell Automation 1775-KA PLC-3 Communication Adapter Module User Manual User Manual

Page 64

Advertising
background image

Addressing Rules and Examples

Chapter 4

4Ć8

For PLC–3 timer and counter files, it is important to note that the data
words are stored in the following order:

CTL PRE ACC

That is, the control, preset, and accumulated values for a given timer or
counter are stored as consecutive words in the same file.

Addressing a Word Range

To address a range of words in PLC–3 memory, use one of the following
formats:

<wordaddr><size>
<filesym>:<offset>,<size>
<wordsym>,<size>

Figure 4.5 is an example of addressing a range of PLC–3 words.

Figure 4.5

Example of Addressing a Range of PLC-3 Words

$N 15 : 0, 20

<

<

Number of words to

Delimiter

Address of first word

be transferred

to be transferred.

10022-I

You may use a word range only as the source field in an assignment
command. The destination must be a file that is as large as, or larger than,
the source range.

Addressing a Word

To address a single word in PLC–3 memory, use one of the following
formats:

Advertising