Appendix

C

CĆ1

Diagnostic Counter Block

At this

byte offset:

This counter is stored:

1.

Bad CRC on acknowledgement [2] (Local error A')

2.

No acknowledgment before timeout occurred (Local error B")

3.

Contention (while master, detected message transmission by

another station)

4.

Acknowledgment contained an error (Local error "C")

5.

Local errors (Sum of A, B, and C above)

6.

Waits (no receive buffer space at destination station)

7.

Timed out (master failed)

8.

False polls (failure to transfer)

9.

Received acknowledgment when not master

10.

Message size too small (less than 5 bytes)

11

Incorrect DST, or SRC = DST

12.

Memory not available for receive buffer

13.

Received message has bad CRC value [2]

14.

Message too long

15.

Message arrived when no buffer space left

16.

Retransmissions of previously received message

17.

Aborts (result of line noise)

18, 19.

Messages successfully transmitted

20, 21.

Messages successfully received

22, 23.

Command messages sent

24, 25.

Reply messages received

26, 27.

Command messages received

28, 29.

Reply messages sent

NOTES:

[1] The address of the first byte of the counter block can be determined by using the diagnostic

status command. Addresses of the other bytes listed here can be derived by adding the

appropriate number of bytes to the staring address of the counter block.

[2]

An acknowledgment is part of the data highway protocol.

Data Highway Port Counters