Remote Error Codes Received from the
1773-KA Module
Appendix B
BĆ13
Error
Error
Code
Type
Meaning
4.First word of destination location does not exist.
237
reply
For all PLC-3 read and write commands:
1.Any word in the total transaction does not exist in
the destination file.
2.The source and destination files are not the same
size.
238
reply
For all PLC-3 read and write commands:
The file size decreased between packets of a
multi-packet transaction and became too small for
the total transaction.
239
reply
For all PLC-3 read and write commands:
File is larger than 65,535 words.
240
reply
For all PLC-3 read and write commands:
Sum of total transaction size and the word
241
reply
For all PLC-3 write commands:
Remote station does not have access to the
destination file.