Rockwell Automation 1775-KA PLC-3 Communication Adapter Module User Manual User Manual
Page 188

Message Formats
Appendix A
AĆ26
Diagnostic Read
You use this command to read up to 244 bytes of data from the PROM or
RAM of the station interface module. You can use it to read the module’s
diagnostic timers and counters. Use the diagnostic status command to
obtain the starting address of the diagnostic counters.
Command Format:
FNC
DLE SRC
STX
DST
C
06
S
TNS
MD TS
TNS
DLE ETX
BCC
01
SIZE
ADDR
Reply Format:
DLE C
S TNS
MD TS
TNS
STX
DLE ETX BCC
DATA - Max of 244 bytes
DST SRC
46
Diagnostic Status
You use this command to read a block of status information from the
station interface module. The reply to this command contains the status
information in its DATA field.
Command Format:
FNC
DLE SRC
STX
DST
C
06
S
TNS
MD TS
TNS
DLE ETX
BCC
03
Reply Format:
DLE C
S TNS
MD TS
TNS
STX
DLE ETX BCC
DATA - Max of 244 bytes
DST SRC
46
The status information varies with the type of station interface module.
Table A.B describes this status DATA for 1775–KA modules.