Installation

Chapter 2

2Ć32

Figure 2.13

Example of a Rung that Sends a Message during switchover from primary PLC-3 to backup

PLC-3.

EN

MSG
MESSAGE TYPE
CTL = FB200:00001 = 0
CHANNEL: E2.5.
#H045$N4:17= $B3:5

DN

ER

00

E0000

00

01

S0003

17

1

STAT

12

STAT

15

STAT

13

E0000

E0000

E0000

00

01

E0000

L

17

01

E0000

U

S0003

NOTE: Bits E0000/00 and E0000/01 are internal storage bits. You can use any unused data

table section to reference these bits. Bit S0003/17 is the run/backup bit.

Using Automatic Switchover

After you select the BACKUP OPERATION for a rev. D. (or later)
1775–KA module, you may want to use automatic switchover for your
PLC–3 backup system. During automatic switchover:

the 1775–KA module for the primary PLC–3 processor disables its

Data Highway port.

the 1775–KA module for the backup PLC–3 processor becomes the

address that you selected with the LIST function (rather than the
corresponding address it received during the BACKUP OPERATION).

NOTE: You cannot select the BACKUP OPERATION for a multidrop
modem applications because the modem port will not become disabled
after a PLC–3 processor fault regardless of the switch settings on the
module.