Allocating memory, Editing message procedures – Rockwell Automation 1775-KA PLC-3 Communication Adapter Module User Manual User Manual

Page 76

Advertising
background image

Editing

Chapter 5

5Ć2

Table 5.A

Example of Message instruction Editing

System Prompt

Action

Key Strokes

Start edits.

SED [ENT]

Insert rung.

IR [ENT]

Enter the energize bit for the message

rung. In this case, binary file 0, word 0, bit

0.

-] [- B0:0/0 [ENT]

Enter the message instruction.

MSG [ENT]

ENTER FILE ADDRESS

Enter the address of the file where the

message instruction will reside in memory.

In this case, binary file 1.

FB1 [ENT]

ENTER SYSTEM

ADDRESS OR

SYMBOL

Enter the channel designation for the

1775-KA module. In this case, 2 is the

module status, 5 is the 1775-KA module

type, and 1 is the thumbwheel number of

the module.

E2.5.1 [ENT]

ENTER MESSAGE

TYPE

Enter the message type. This is always 1

for the 1775-KA module.

1 [ENT]

Enter a single 1775-KA assignment

command or the name of a message

procedure. In this case, the name of the

message procedure is PROC_1.

@PROC-1 [ENT]

End edits.

EE [ENT]

Before the 1775–KA module can transfer data to or from any file in
PLC–3 memory, that file must exist and it must have enough memory
allocated to it to accommodate the data transfer. You can create and
allocate a file using the PLC–3 memory management commands. Refer to
the PLC–3 Programming Manual (publication 1775–801) for a description
of memory management.

Table 5.B shows an example of editing a message procedure through an
Industrial Terminal connected to a 1775–S4A module. Table 5.C shows
how to edit the same message procedure through a data terminal
connected to a 1775–S4B module.

Allocating Memory

Editing Message Procedures

Advertising