Rockwell Automation 1775-KA PLC-3 Communication Adapter Module User Manual User Manual

Page 203

Advertising
background image

Remote Error Codes Received from the

1773-KA Module

Appendix B

BĆ11

Error

Error

Code

Type

Meaning

207

local

Word range specified in destination address.

208

local

Destination and source addresses disagree in type.

209

local

Not of data highway message type.

210

local

Use of a non-PLC-3 type address in a local address
operand.

211

local

In an assignment command, one of the local files
does not exist, or the word specified is beyond the
end of the file.

213

local

A local file exists, but the action specified refers to
addresses beyond the end of the file. Possible
causes include:
1.In a word assignment statement, the offset is
greater than the file size.
2.In a word range assignment statement, the sum of
the base address and the offset is greater than the
total file size.
3.In a file assignment statement, the destination file
is smaller than the source file. If the source file is
remote, a single packet will be fetched from the
remote station's file.

214

local

Local source and destination files differ in size.

215

local

The value resulting from operations specified on
the left side of an assignment statement will not fit
into the destination specified on the right side.
1.The source is in the H section and the destination
is in the N section, but the number is too large
(i.e., outside the range -32768 to +32767).
2.A word is transferred from a binary section (I, O,
or B section) to the N or C section and the
high-order bit is a 1.
3.The destination is in the D section, but the
number is not a valid BCD bit pattern.

217

local

More than 8 levels specified in file address.

218

local

File size changed between packets of a multi-
packet transaction.

230

local

Reply packet too small.

Advertising