Network and application layer protocols chapter 12 – Rockwell Automation 1775-KA PLC-3 Communication Adapter Module User Manual User Manual

Page 160

Advertising
background image

Network and Application Layer Protocols

Chapter 12

12Ć13

Figure 12.5

Example of PLC-3 Logical Addressing Format

6

5

4

3

2

1

0

0

1

1

10066–I

1

0

0

0

0

0

0

0

0

0

1

0

1

1

1

1

1

1

1

1

0

0

0

1

0

0

0

0

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

0

PLC–3 Extended Address

Data Table Area = Level 1

Context = Level 2

Section = Level 3

File = Level 4

Offset = Level 5

Word = Level 6

Logical Addressing Format

Always zero

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Level 1 (Default = 3 for date table)
Level 2 (Default = 1 for current context)

Level 3 (Value = 2)
Level 4 (Default = 0)

Level 4 (Value = 260)

Level 5 (Default = 1)
Level 6 (Value = 0)

Byte 1 –– is the flag byte. In this case it indicates that the addresses for levels 3, 4, and 6 are specified in the

bytes that follow. Default values are used for the levels 1, 2, and 5.

Byte 2 –– is the value of the level–3 address.

Byte 3 –– is a delimeter that says the next two bytes are one address.

Byte 4 –– is the low byte of the level–4 address.

Byte 5 –– is the high byte of the level–4 address. Note that bytes 4 and 5 together give a value of 260 for the

level–4 address.

Byte 6 –– is the value of the level–6 address. Even though it is the default value, it must be specified because

it is the last level in the desired extended address.

E3 . 1 . 2 . 260 . 0 . 0

Flag bit for level:

Advertising