Message Formats

Appendix A

AĆ29

Set NAKs

Use this command to set the maximum number of NAKs that the station
interface module will accept per message transmission. Put the number in
the DATA field. The default setting for the KE/KF module is 3 NAKs per
transmission.

Command Format:

FNC

DLE

SRC

STX

DST

C

06

S

TNS

MD

TS

TNS

DLE ETX

BCC

05

DATA

Reply Format:

DLE

SRC

STX

DST

C

46

S

TNS

MD

TS

TNS DLE ETX

BCC

Set Timeout

Use this command to set the maximum amount of time that the station
interface module will wait for an acknowledgment to its message
transmission. The setting is expressed as the number of cycles of an
internal clock, where 40 cycles equals 1 second. Put the number of
desired cycles in the DATA field. The default setting for the KE/KF
module is 128 cycles, or about 3 seconds.

Command Format:

FNC

DLE

SRC

STX

DST

C

06

S

TNS

MD

TS

TNS

DLE ETX

BCC

04

DATA

Reply Format:

DLE

SRC

STX

DST

C

46

S

TNS

MD

TS

TNS DLE ETX

BCC