1-2 Module Overview

Module operation is determined by selections made in the Setup and
Control Word (M0:e.1). Setting the Function Control bit to 1 triggers
the module to start the proper pulse counter, rate measurement, and
output control functions. Many parameters are dynamic and can be
changed without disrupting counter operation.

A block diagram of the module is shown below. Inputs from the
terminal block enter the diagram at the left, outputs to the terminal
block exit at the right. M0 and Output file parameters from the SLC
enter the logic blocks from the top. Input file data to the SLC exit the
logic blocks from the bottom.

Input

Logic

A
B

Counter Input

Parameters

Pulse

Counter

Pulse Counter Parameters

Pulse and Direction

Operating Mode Logic

Operating Mode Parameters

Range

Sequencer

Rate

Accumulated Count

Rate

Counter

Rate Period Parameters

Pulse

Counter

Inputs

Reset
Logic

Z

LS

Reset Parameters

LS Filter (JW1)

Reset Condition

Reset

Input

Bit

Rate

Counter

Inputs

Rate Measurement

Operating

Mode

Inputs

Operating

Mode

Outputs

Output

Control

Logic

Output Control

Parameters

Output

Status

Inputs

From Terminal Block

To

Terminal Block

4

Physical

Outputs

Counter Input Parameters

Input Type (M0:e.1/9–11)
Up/Down Count Direction (M0:e.1/3)

–d

Reset Parameters

Soft Reset bit (M0:e.1/4)

–d

Reset Mode (M0:e.1/5–7)

Rate Period Parameters

Rate Period (M0:e.9/0–7 or M0:e.16/0–7)

–d

Operating Mode Parameters

Operating Mode (M0:e.1/14–15)
Function Control Bit (M0:e.1/12)
Range Definitions:

Range Starting Values (M0:e.10 – 33)

–d

Range Ending Values (M0:e.10 – 33)

–d

Range Outputs (M0:e.3 – 8)

–d

Valid Ranges (M0:e.2)

–d

Sequencer Definitions:

Valid Steps (M0:e.2 and M0:e.3/0–7)

–d

Step Presets (M0:e.17 – 40)

–d

Step Outputs (M0:e.4 – 15)

–d

Initial Outputs (M0:e.3/8–15)

–d

Sequencer Reset (M0:e.1/0)

–d

Pulse Counter Parameters

Reset Value (M0:e.34 or M0:e.41)

–d

Maximum Count Value (M0:e.34 or M0:e.41)
Counter Hold bit (M0:e.1/2)

–d

Counter Type bit (M0:e.1/13)

Output Control Parameters

Direct Outputs (O:e.0/0–7)

–d

Output Source Select (M0:e.0/0–7)

–d

Enable Outputs bit (M0:e.1/1)

–d

Rate Counter Inputs

Rate Valid (I:e.0/3)
Rate Counter Overflow (I:e.0/4)
Rate Measurement Overflow (I:e.0/5)
Zero Rate Period Count (I:e.0/2)
Rate Period Count (I:e.2)
Rate Measurement (I:e.3)

Pulse Counter Inputs

Accumulated Count (I:e.1)
Overflow/Underflow (I:e.0/13)
Pulse Counter State (I:e.0/14–15)

Reset Input bit (I:e.0/12)

Operating Mode Inputs

Sequencer Inputs

Current Sequencer Step (I:e.5/0–7)
Next Sequencer Step (I:e.5/8–15)
Sequence Done (I:e.0/6)

Range inputs

Ranges Active (I:e.6/0–11)

Output Status Inputs (I:e.4/8–15)

Error Inputs

Critical Error (I:e.0/10)
Configuration Error bit (I:e.0/11)
Configuration Error Code (I:e.4/0–7)

–d indicates a dynamic parameter