Page 36
Publication 1746-UM006B-EN-P - August 2005
2-18 Module Operation
In this example, four ranges are specified. Configuration data for the
counter is shown in the table. It indicates that output 0 is on for
counts within range 1, output 1 is on for counts within range 2, output
2 is on for counts within range 3, and both outputs 0 and 3 are on for
counts within range 4. When the count is 2000, outputs 2 and 1 are
on, since 2000 falls within ranges 2 and 3.
The figure below demonstrates Range Mode when a ring counter is
used.
Range Mode with Ring Counter
Range
Starting
Value
Ending
Value
Outputs
(1)
(1) Bits 0-3 are physical outputs, bits 4-7 are soft outputs.
Outputs On
7 6 5 4 3 2 1 0
1
10,000
12,500
0 0 0 0 0 0 0 1 0
2
200
8,000
0 0 0 0 0 0 1 0 1
3
32,000
500
0 0 0 0 0 1 0 0 2
4
20,000
23,000
0 0 0 0 1 0 0 1 0 and 3
Range
4
•
Range
3
Range
2
Range
1
1
32,767
32,000
200
500
8,000
10,000
12,500
20,000
23,000