Limit switch wiring (24v dc hard contact), Limit switch wiring (12v dc hard contact), Limit switch wiring (5v dc solid state) – Rockwell Automation 1746-HSCE,D17466.5 High-Speed Counter Module User Manual
Page 59: Ugh 3-15
Advertising

Publication 1746-UM006B-EN-P - August 2005
Installation and Wiring 3-15
Limit Switch Wiring
(24V dc Hard Contact)
Limit Switch Wiring
(12V dc Hard Contact)
Limit Switch Wiring
(5V dc Solid State)
HSCE module
+
–
24V dc
Hard Contact
LS (24V dc)
LS (12V dc)
LS (5V dc)
LS COM
JW1
3 2 1
Limit Switch
COM
VS
Do not connect LS (5V dc) or LS (12V dc) Terminals
Jumper placed for 10 ms filtering
HSCE module
+
–
12V dc
Hard Contact
LS (24V dc
LS (12V dc)
LS (5V dc)
LS COM
JW1
3 2 1
Limit Switch
COM
VS
Do not connect LS (5V dc) or LS (24V dc) Terminals
Jumper placed for 10 ms filtering
HSCE module
+
–
5V dc
Solid State
LS (24V dc)
LS (12V dc)
LS (5V dc)
LS COM
JW1
3 2 1
Limit Switch
COM
VS
VS COM OUT
Do not connect LS (12V dc) or LS (24V dc) Terminals
Jumper placed for 300 microseconds filtering
Advertising