4-6 Configuration and Programming

M0:e.1 Bit 4 - Soft Reset (Dynamic)

The Soft Reset bit can be used to reset the counter in combination with
the physical reset signals. Setting this bit (to 1) resets the counter, via
the Reset Mode bits, if Soft Reset (bit 7) is selected. The 0 to 1 transition
of the Soft Reset condition (M0:e.1/5-7) resets the counter when
configured to do so (refer to Counter Reset Control in Chapter 2).

M0:e.1 Bits 5,6,7 - Reset Mode (Static)

These bits allow you to select the device(s) that reset the counter. Bit
5 enables the Z reset, Bit 6 enables the limit switch reset, and bit 7
enables the soft reset, as shown below:

IMPORTANT

The Soft Reset bit must be held at 1 until the counter
resets. The Reset Input bit (I:e.0/12) can be used to
detect a counter reset.

Setup and Control Word bits

Reset Condition is True

7

6

5

0

0

0

Never

0

0

1

When Z is ON

0

1

0

When the limit switch is ON

0

1

1

When the limit switch and Z are ON

1

0

0

When the Soft Reset is 1

1

0

1

When the Soft Reset is 1 and Z is ON

1

1

0

When the Soft Reset is 1 and limit switch is ON

1

1

1

When the Soft Reset is 1, limit switch and Z are ON

Setup and Control Word, Word 1

Bit Number (decimal)

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Resets Counter via
Soft Reset

Enables Soft Reset

M0:e.1

R

R

Setup and Control Word, Word 1

Bit Number (decimal)

Reset Mode bits

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Z Reset

Limit Switch

Soft Reset

M0:e.1

R

R

R