6-28 Application Examples
The following is a brief description of the application.
•
The Initial Outputs (M0:e.3/8-15) are reset to 0. Therefore, the
brake is enabled (the clutch is disengaged) and the cutter is
retracted.
•
The user program starts the motor. The encoder begins to send
pulses to the module.
•
After 100 counts, the module releases the brake (O:1/2), which
engages the clutch.
•
At count 150, the high-speed motor output (O:1/1) is energized.
•
At count 14000, the high-speed motor output (O:1/1) is
de-energized.
•
At count 18000, the brake is enabled (which disables the clutch)
and the cutter is energized.
•
At count 19000, the cutter is de-energized and the sequencer
rolls over. The process repeats, as indicated below by the repeat
point.
High Speed
O:1/1
O:1/2
O:1/3
Cutter
Motor Enable
O:1/0
100
150
14,000
18,000
19,000
1
0
1
0
1
0
1
0
Accumulated
count
0
Repeat Point
Power up
User program starts motor.
Module releases brake
Encoder starts sending pulses
Clutch engages
Motor switches to high speed
Motor switches to low speed
Brake enabled (cluth disengages)
Cutter is energized
Cutter is de–energized
Clutch
1
/ Brake
0