Rockwell Automation 1746-HSCE,D17466.5 High-Speed Counter Module User Manual

Page 175

Advertising
background image

Publication 1746-UM006B-EN-P - August 2005

Sequencer Mode Configuration Worksheets E-5

Output Status and Configuration Error Code (page 4-43)

Next Sequencer Step and Current Sequencer Step (page 4-44)

Next Sequencer Step Preset (decimal) (page 4-45)

Module Setup Information

Module ID Code = 12705 (8 Input and 1 Output word)
File Size - 42 word integer file, and 42 word M0 File

I:e.4

7

6

5

4

3

2

1

0

Bit Number (decimal)

15

14

13

12

11

10

9

8

Output Number

7

6

5

4

3

2

1

0

Output Status and Configuration Error Code

0000 = no error
0001 = not defined
0010 = Max Count equals 0 (ring)
0011 = Invalid Operating Mode
0100 = Invalid Input Type
0101 = Static Parameter Changed
0110 = Ranges Active equals 0
0111 = Rate Period equals 0
1000 = Linear Counter Reset Value out of range
1001 = Sequencer Preset > Maximum Count

Configuration Error Code

R R

R R

0 = output OFF
1 = output ON

Output Status

Outputs 0 thru 3 relate to Physical Outputs
Outputs 4 thru 7 relate to Soft Outputs

I:e.5

7

6

5

4

3

2

1

0

Bit Number (decimal)

15

14

13

12

11

10

9

8

Next Sequencer Step

Current Sequencer Step

I:e.7

Next Sequencer Step Preset

Advertising