I:e.5 reserved, I:e.5 reserved -22 – Rockwell Automation 1746-HSCE,D17466.5 High-Speed Counter Module User Manual
Page 82

Publication 1746-UM006B-EN-P - August 2005
4-22 Configuration and Programming
I:e.4 Bits 0 through 7 - Configuration Error Code
I:e.4 Bits 8 through 15 - Output Status
These bits reflect the current state of both the Soft and Physical
Outputs. If the Enable Output bit (M0:e.1/1) is false or if the processor
is not in run mode, the Physical Outputs are not active.
Bits 8-11 represent the Physical Outputs 0-3. Bits 12-15 represent the
Soft Outputs 4-7.
I:e.5 Reserved
Configuration
Error Code
Reason
Critical
Error
Action
Hex Binary
01
0000 0001 not defined
-
reconfigure
(1)
(1) The Function Control bit must be reset to 0, the parameter must be changed, and the Function Control bit is
then set to 1
.
02
0000 0010 max count = 0 (ring)
yes
reconfigure
03
0000 0011 invalid operating mode
yes
reconfigure
04
0000 0100 invalid input type
yes
reconfigure
05
0000 0101 static parameter changed
yes
reconfigure
06
0000 0110 ranges active = 0
no
change parameter
07
0000 0111 rate period = 0
no
change parameter
08
0000 1000 linear counter reset value out of range
no
change parameter
09
0000 1001 sequencer preset > max. count
no
change parameter