Rockwell Automation 1746-HSCE,D17466.5 High-Speed Counter Module User Manual

Page 88

Advertising
background image

Publication 1746-UM006B-EN-P - August 2005

4-28 Configuration and Programming

M0:e.1 Bits 5,6,7 - Reset Mode (Static)

These bits allow you to select the device(s) that reset the counter. Bit
5 enables the Z reset, Bit 6 enables the limit switch reset, and bit 7
enables the soft reset, as shown below:

You can reset the sequencer to the Initial Output pattern (M0:e.3/8-15)
using the Sequencer Reset bit (M0:e.1/0).

Setup and Control Word bits

Reset Condition is True

7

6

5

0

0

0

Never

0

0

1

When Z is ON

0

1

0

When the limit switch is ON

0

1

1

When the limit switch and Z are ON

1

0

0

When the Soft Reset is 1

1

0

1

When the Soft Reset is 1 and Z is ON

1

1

0

When the Soft Reset is 1, and limit switch is ON

1

1

1

When the Soft Reset is 1, limit switch and Z are ON

R

Setup and Control Word, Word 1

Bit Number (decimal)

Reset Mode bits

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Z Reset

Limit Switch

Soft Reset

M0:e.1

R

R

R