Publication 1746-UM006B-EN-P - August 2005

2-20 Module Operation

When using Rate Mode, use the Ring Counter and set the Reset
Value/Maximum Count Value (M0:e.34)) to 32,767. Doing so allows
the counter to roll over after reaching 32,767. If the Linear Counter
counts beyond 32,767, it will cause an overflow (as explained in
Linear Counter Overflow/Underflow located in Chapter 5).

Rate Mode with Linear Counter

IMPORTANT

Appendix D contains blank worksheets to assist you
when configuring your module for Rate Mode
operation.

ATTENTION

If the input pulse rate is above 32767 Hz, a RAte
Measurement Overflow occurs. The Rate
Measurement Overflow bit (I:e.0/5) will then be set
to 1. Refer to Rate Measurement Overflow located in
Chapter 5.

Output 2

Output 1

Output 0

Output 3

off

on

Range 3

Range 2

Range 4

Range 1

Range 4

–32,767

+32,767

Counter Value

0

Range

Starting
Value

Ending
Value

Outputs

(1)

(1) Bits 0-3 are physical outputs, bits 4-7 are soft outputs.

Outputs On

7 6 5 4 3 2 1 0

1

-7000 Hz

-5000 Hz

0 0 0 0 0 0 0 1 0

2

-1000 Hz

+4500 Hz

0 0 0 0 0 0 1 0 1

3

-4000 Hz

+3000 Hz

0 0 0 0 0 1 0 0 2

4

+20,000 Hz

-20,000 Hz

0 0 0 0 1 0 0 1 0 and 3