3-2 Installation and Wiring

Dip Switch and Jumper
Locations

Two dip switches (SW1 and SW2) and one jumper (JW1) are located
on the side of the module.

•

SW1 selects the type of input (single ended or differential).

•

SW2 selects the output voltage range (4.5-10V dc or 10-30V dc).

•

JW1 selects the filtering rate (300 µs or 10 ms) used to debounce
the limit switch input.

Default settings are shown below:

ATTENTION

Use a small screwdriver to change dip switch
positions. Graphite from pencils will damage the
switch.

SW2

JW1

SW1

1

234

N

JW1

O

1234

N

O

SW2

SW1

1

3

10-30V dc

SW2 Default

10 ms Filter

JW1 Default

Single Ended Operation

SW1 Default