Sw2 settings, Sw1 settings, Sw2 settings -3 sw1 settings -3 – Rockwell Automation 1746-HSCE,D17466.5 High-Speed Counter Module User Manual
Page 47

Publication 1746-UM006B-EN-P - August 2005
Installation and Wiring 3-3
SW2 Settings
Select an output voltage range that coincides with your supply
voltage. The selections are 4.5-10V dc or 10-30V dc.
SW1 Settings
Select an input connection, single ended or differential.
It is possible to configure different inputs in different modes. For
example, input A (CHA) can be configured as differential and input Z
(CHZ) can be configured as single ended.
ATTENTION
All switches of SW2 must be ON or all switches must
be OFF. Permanent damage may result if some are
ON and some are OFF.
Operating in the 10-30V dc range with the switches
set for the 4.5-10V dc range will damage the module.
Switch
Output
1
2
3
4
0
1
2
3
1 2 3 4
1 2 3 4
ON
OFF
ON
OFF
10-30V dc
4.5-10V dc
Position
ON
OFF
Input connection
differential
single-ended
Input ON range
2.8–4.5V dc
3.1–5.5V dc
Switch
Channel
1
2
3
4
A
B
Z
not used
1 2 3 4
ON
OFF
Dip switch SW1